Cable for a building

Answer a few questions about the building, its rooms and appliances — the site picks the cable mark and cross-section for every circuit, the breaker rating and the length, builds a specification in the factory’s sizes and passes it to a price request or Excel.

  1. 1Building
  2. 2Rooms and circuits
  3. 3Cable requirements
  4. 4Result
What are you wiring?

The type sets the usual rooms and defaults — everything can be changed later.

From the supply contract. Leave empty for the usual value of such a building: 10 kW.

Supply line

How the cable reaches the panel — it decides the mark and the size.

The calculation is an estimate. Circuit sizes follow PUE table 1.3.6 (copper cable in air, × 0.92 for three phases) and the voltage drop, but never go below the minimum of СП 256.1325800 (lighting 1.5 mm², sockets 2.5 mm², a one-phase cooker 6 mm²); conductors in dwellings are copper (PUE 7.1.34). The breaker comes from the standard row: load current ≤ rating ≤ allowed current of the cable (PUE 3.1.9–3.1.11). The supply line is sized for the larger of the allocated and the design power, СИП-2 by its own current table. The design power is the sum of the circuits’ powers with demand factors. The final choice is the designer’s; the factory’s manager checks the specification on request.